News arrow Products arrow Diagnostics tools arrow PROFIBUS Analyser BC-400
PROFIBUS-Analyser BC-400

The compact network all-rounder

The PROFIBUS-Analyser BC-400 allows analysing and optimizing PROFIBUS networks.

Perfect fields of application
To increase the plant availability by regular testings during operation.

Convincing and varied
With the PROFIBUS-Analyser BC-400 you can monitor the network continuously, detect errors in time, already before they occur as well as analyse configuration errors. Thanks to its compact design, this device is ideal even for mobile applications.
The comprehensive online diagnostics function records all essential parameters of a PROFIBUS network continuously and displays them referring to devices. Important events are recorded in a log and shown fort he entire bus or referring to devices.

Technical highlights
Status display of each bus device
Comprehensive online analysis of all essential parameters of a PROFIBUS network
Log function for the entire bus or referring to devices
Recording and displaying filter
Trigger function with hardware input and output
Telegram decodation for FDL, DP, DP-V1, DP-V2
USB interface in robust aluminium case for mobile applications

Order data

PROFIBUS Analyzer BC-400

PROFIBUS Analyzer BC-400
€1.580,00
Add to Cart
  

Accessories
PROFIprobe

Technical data

Supported operating systemsWindows 2000, XP, Vista
Hardware requirementsPC or notebook, CPU with at least 1 GHz, USB interface
Protection typeIP 20
Supply voltageVia USB
Power consumptionMax. 500 mA
Operating temperature0 °C to 55 °C
Storage/transporting temperature-20 °C to 70 °C
PROFIBUS interface RS-4859-pin SUB-D connector, galvanically isolated
9.6; 19.2; 45.45; 93.75; 187.5; 500; 750 Kbps; 1.5; 3; 6; 12 Mbps
Live listDisplay of the live list as tree with master/slave allocation, matrix for displaying relevant parameters (e.g. telegram repeats) for all devices
Online diagnostics on bus levelToken time of circulation, bit, byte and telegram errors
Online diagnostics for every masterDuration of the cyclic data exchange, idle time 1, idle time 2, slot time
Online diagnostics for every slaveCommunication status, allocated masters, ident number, station delay time, I/O data with configured and actual length, parameterizing data, configuration data, diagnostics messages (circular buffer), statistics about DP-V0 services, negative and erroneous replies, telegram repeats per poll cycle and in total
Telegram recordingImmediate recording in circular buffer with saving possibility, long-run recording into files
Recording filter, display filterFiltering to station addresses, FDL telegram formats, erroneous telegrams, telegram repeats, FDL services, DP-, DP-V1- and DP-V2 services
TriggerTriggering to station addresses, FDL telegram formats, erroneous telegrams, telegram repeats, FDL services, DP, DP-V1 and DP-V2 services
Telegram displayDecodation for FDL, DP, DP-V1, DP-V2, freely selectable colour mode for any service, time stamp absolute or time since measuring start as well as telegram distance and telegram pauses
 