The ACCON-MPI-Adapter allows the connection of a PC via its serial interface to the MPI interface of a S7 PLC. If you prefer to use the Ethernet interface instead of the serial interface of your PC, you can thereby use a higher transmission speed. For this we recommend the ACCON-NetLink-PRO compact.

Perfect fields of application

  • As programming adapter to create and change the PLC program
  • As communication adapter for visualizations
  • As communication adapter to access the PLC's data

Varied ranges of application

  • Programming S7 PLCs with STEP 7
  • Connecting visualizations with S7 PLCs
  • Logging S7 data (e.g. with ACCON-EasyLog)

Convincing and varied

The ACCON-MPI-Adapter RS-232 uses the same communication protocol as the PC adapter. Thus, the ACCON-MPI-Adapter RS-232 can be used with any software supporting the PC adapter.

Technical highlights

  • Low-cost solution for programming and visualization
  • Serial transmission rate up to 115.2 Kbps
  • MPI speed up to 187.5 Kbps
  • Voltage supply from the CPU
  • External 24 VDC voltage feed possible
  • Made in Germany

Note:
Starting with STEP 7 version 5.5 SP2, Siemens no longer supports serial COM ports under Windows 7 64-bit. The Siemens TIA Portal also no longer supports any COM ports - regardless of which operating system it is installed on! We will be happy to advise you about alternatives.

Connection to the PC RS-232 with 9-pin SUB-D socket, via included null modem cable (approx. 2 m), max. 115.2 Kbps
Connection to the PLC 9-pin SUB-D plug, cable stationary mounted (ca. 1.2 m), max. 187.5 Kbps
Supported PLCs S7-300, S7-400
Weight in kg approx. 0.18
Dimensions (W x H x D) in mm 54 x 105 x 30
Protection type IP 20
Supply voltage 24 VDC ±25 %
External voltage feed possible Yes, e.g. with this external power supply
Power consumption 30 mA (typ.) / 45 mA (max.)
Operating temperature 0 °C to 60 °C
Storage/transporting temperature -20 °C to +60 °C
Allowed relative humidity Operating 5 % to 85 % at 30 °C, storage 5 % to 93 % at 40 °C
German manual ACCON-MPI-Adapter
ACCON-MPI-Adapter_HB_de.zip 221 KB September 29, 2008
English manual ACCON-MPI-Adapter
ACCON-MPI-Adapter_HB_en.zip 228 KB March 09, 2009

Can the functionality of an ACCON-MPI-Adapter RS-232 be tested with the ACCONfigurator?

There is an "available participants" feature in the toolbar. This function can be used to display the reachable participants.


On the adapter, the polarity for the external power supply is no longer legible. How can I determine it instead?